Construction |
 |
The centre provides 4,405 m² of various grades of space sub-divisible down to 25 m² caged modules. |
 |
The base construction is from 1981, and has since benefitted from substantial refurbishment and infrastructure upgrades |
 |
Good space utilisation with generous internal column spacing |
 |
Heavy duty floor loading capacity, high capacity in key areas |
 |
Range of floor to ceiling heights up to 4.0 m available |
| |
|
| |
Building Design |
 |
Master plan caters for substantial conditioned module, office and associated spaces together with other space available for fit out to customer specification |
 |
Particular customer specifications can be incorporated including Electromagnetic Protection, fire suppression and special power supply arrangements |
| |
|
| |
Power |
 |
7.6 MVA installed provision increasable to 12 MVA. |
| |
|
| |
Conditioned Power |
 |
Two x 2.2MVA dual output diesel rotary UPS systems, providing 1.8 MVA of UPS in “diverse” power configuration. |
 |
Scalable UPS building to a maximum of 4 MVA in 250KVA blocks providing either “diverse” power or “redundant” power supply systems to Customer modules. |
 |
Further modular UPS building to a maximum of 2.8 MVA in 350 KVA blocks providing “redundant” power supply systems to Customer modules. |
 |
-48 VDC redundant power |
| |
|
| |
Emergency Power |
 |
Two x 2.2MVA dual output diesel rotary UPS systems, providing 1.6MVA of short break power supplies with 24,000 litre fuel storage capacity. |
 |
Two x 2.2MVA diesel standby power generators supporting scalable UPS and short break supplies, with further 24,000 litre fuel storage capacity |
 |
Five synchronised 1.0 MVA diesel standby power generators supporting modular UPS and short break supplies, with further 24,000 litre fuel storage capacity |
| |
|
| |
HVAC |
 |
Conditioned modules are supported by six redundant 1 MW chillers feeding in-module redundant close control units. Total capacity 4.2 MW in a redundant configuration. |
 |
‘Free’ cooling chiller configuration capable of 100% cooling duty in Wintertime |
| |
|
| |
Fibre Infrastructure |
 |
Carrier neutral host to multiple independent fibre carriers |
 |
Provision of diverse underground fibre entry points |
 |
12 X 100 mm fibre ducts for access to three secure Carrier Connection Rooms with provision for a third diverse point of entry |
| |
|
| |
Elevators |
 |
Two passenger and goods service lifts, one with ‘high car’. |
| |
|
| |
Fire protection |
 |
High grade very early smoke detection apparatus in conditioned modules |
 |
Argonite fire suppression system in conditioned modules |
 |
Monitored automatic smoke detection throughout |
| |
|
| |
Security |
 |
On site 24 hour 365 day manned security presence |
 |
Security operates from purpose built security bunker |
 |
Internal and external advanced security surveillance camera systems |
 |
Intruder detection and card access systems throughout |
 |
High grade 360° perimeter fencing with secure access control |
| |
|
| |
Roof space & Parking |
 |
Substantial satellite / antennae space with good line of sight vantage |
 |
Secure surface parking for 54 cars |
| |
|
| |
Accessibility |
 |
City Centre: 6 km |
 |
Airport: 70 km |
 |
Airport Express: 6 km |
 |
Rapid Transit: 0.3 km |
| |
|