Digiplex Header Image








Locations & Specifications Summery - London 1

Construction | Building Design | Power | HVAC | Elevators | Fire Protection | Security |
Fibre Infrastructure | Roof Space & Parking | Accessibility

  Construction
The centre provides 1,900 m_ of high grade ITH space with expansion up to 3,600 m_ sub-divisible down to 25 m_ caged modules.
The base construction is from 1987 and has since benefited from substantial refurbishment and upgrade.
Good space utilisation without internal columns
Heavy Duty floor loading capacity
Floor to ceiling heights 4.0 m
   
  Building Design
Master plan caters for substantial conditioned module, office and associated spaces together with other space available for fit out to customer specification
Includes infrastructure to meet Super Computer requirements
Particular customer power specifications can be incorporated.
   
  Power
7.0 MVA 11 kV internal distribution, increasable to 12.0 MVA
   
  Conditioned Power
Modular UPS providing “redundant” power supply systems to Customer modules.
   
  Emergency Power
Initially 4.0 MVA diesel standby power generators as N+1 with 18,000 litre fuel storage capacity
Master development plan designed to deliver 7 MVA diesel driven standby power generators
   
  HVAC
Service corridor mounted down flow units configured as N+2. Dual coil DX with 'free' cooling heat rejection to cooling water ring and external dry coolers.
‘Free’ cooling coil in CCU using 'free' cooled dry cooled water capable of 100% cooling duty in Wintertime
Masterplan contains N+N chilled water circuit for Hydro Clusters.
Water cooling outlets for Main Frame and super computer can be incorporated to customer requirement.
   
  Fibre Infrastructure
Carrier neutral host to multiple independent fibre carriers
Provision of diverse underground fibre entry points
Fibre ducts for access to two secure Carrier Connection Rooms
   
  Elevators
One goods lift
   
  Fire protection
High grade very early smoke detection apparatus in conditioned modules
Fire suppression system in conditioned modules
Monitored automatic smoke detection throughout
   
  Security
On site 24 hour 365 day manned security presence
Security operates from purpose built security office
Internal and external advanced security surveillance camera systems
Card access systems throughout
Campus based zone within zone access control
   
  Roof space & Parking
Substantial satellite / antennae space with good line of sight vantage
Secure surface parking for 100's of cars
   
  Accessibility
London Heathrow 18 miles
Central London via train 30 mins
Just off Junction 8 of M1.